Mold And Microbial Contamination
Mold has become a hot topic recently among property
owners, health and safety professionals, and regulators.
While the debate goes on over how much of the hysteria
is hype and how much is based on science, property owners
must become knowledgeable about the threat of mold and
how they can protect building occupants and reduce their
liability. While “mold” is the word most
commonly used in these discussions, microbial contamination
can include not only molds but also yeasts, bacteria,
and other microorganisms, all of which can cause health
problems by producing allergens, irritants, and toxins
when their spores are inhaled or touched, particularly
by sensitive individuals. Mold can also exacerbate asthma
and cause eye, skin, and respiratory irritation.
How Does Mold Become A Problem?
Microorganisms are present in all but the cleanest air,
such as in a clean room operation. Spores can lay dormant
at most temperatures and moisture levels. The hazard
to building occupants comes when those spores are amplified.
Amplification occurs when a spore is present with the
right temperature, moisture and nutrient source. If
amplification occurs in an area with poor ventilation,
the microorganisms can become airborne, forming an inhalation
hazard to those present in the growth area.
Indoor moisture can come from a variety of sources,
including rainwater, plumbing leaks, kitchen spills,
or humidity. Rainwater can penetrate buildings from
roof leaks, poor flashing, deficient masonry pointing,
porous wood, or inadequate grading which does not divert
surface water from the building. Plumbing leaks can
occur in both fresh water and sewer piping in wall or
floor cavities as well as piping buried under slabs
or encased in concrete, which can wick through the concrete
to the building interior. Indoor relative humidity levels
should be between 30 percent and 60 percent. Temperature
extremes should be avoided, particularly high temperatures
above 70o F. Inadequate climate controls can be a major
factor in microbial contamination when inadequate fresh
air is taken in to save heating and cooling expenses,
if zones such as auditoriums are not heated or cooled
when not in use, or if an HVAC unit is undersized and
cannot extract enough moisture from the air. Nutrients
can be provided by cellulose material such as paper,
wood, ceiling tiles, cardboard; dirt and dust; and glues
such as those found in wallpaper paste.
Prevention
To prevent microbial amplification, building owners
need to address one of the components (nutrients, moisture,
and temperature) of microbial amplification as all three
are needed to prevent mold growth. It is not practical
to eliminate nutrients, as paper and wood are common
in most buildings. However, if a building or part of
a building is prone to high moisture (such as kitchens,
semi-protected loading docks, and washrooms), nonporous,
inert materials such as glass, ceramics, plastics, and
metal should be used. Maintaining temperature can be
done by ensuring adequate HVAC systems are installed
and a preventive maintenance program is employed. The
most effective method to reduce microorganism amplification
is moisture control. Moisture control begins during
construction. Building owners should ensure that contractors
have quality control procedures and adequate insurance.
Porous materials (drywall, carpet) should not be installed
before the building is tight. After construction, moisture
controls can include regular inspections of mechanical
systems, exterior protection (roofing, flashing, pointing),
basements, sumps, and regular walkthrough inspections.
High humidity areas such as shower rooms, laundry rooms
or indoor pool areas should be provided with ventilation
fans which discharge to the exterior.
Management Controls
Management can take some preventive measures beyond
the previously-mentioned building maintenance tasks.
If a building is leased to a tenant, the owner should
state in the lease agreement who has responsibility
for the building’s mechanical systems, including
temperature and humidity ranges which must be maintained.
The owner should also require that the owner or their
representatives conduct an annual inspection to check
for moisture conditions or visible microbial growth.
The owner should also require the tenant to promptly
report any moisture or microbial growth conditions as
well as any claims related to these conditions. If a
concern or complaint is received by the owner, it should
be documented and action should be taken as soon as
practical. The owner or an authorized representative
should conduct a visual inspection of the complaint
area and inspect for visible moisture or microbial growth.
If moist conditions are observed, they should be corrected
as soon as possible by fixing leaks, repairing roofs,
or regrading. If extensive microbial growth is observed
or if health complaints are received, a qualified indoor
air quality consultant should be retained to assess
the situation. Building owners should conduct periodic
audits of property management records and internal staff
and external contractor practices.
Remediation
In the event of water damage, prompt action is essential.
Cleanup operations should be conducted within 48 hours.
Hard surfaces should be dried and water-damaged porous
surfaces such as drywall should be discarded. If action
is not taken in a timely manner, porous surfaces such
as carpets and furniture may also have to be discarded.
Comprehensive mold regulations have not yet been developed;
however, detailed procedures for mold remediation may
be found in the US Environmental Protection Agency (USEPA)
guidance document Mold Remediation in Schools and Commercial
Buildings and in the New York City Department of Health
(NYDOH) Guidelines on Assessment and Remediation of
Fungi in Indoor Environments. These guidance documents
provide suggestions for what should be discarded, how
drying should be conducted, how to prevent microbial
migration to other areas, investigation protocols, clearance
sampling, and protection of remediation personnel. Extensive
remediation should be performed by qualified contractors
with adequate insurance coverage affiliated with professional
organizations. Check references and ensure that USEPA,
NYDOH, or other guidelines are followed.
While it is not possible to completely eliminate microorganisms
in occupied spaces, control of temperature, nutrients
and, most importantly, moisture, can prevent microorganism
amplification. Policies and procedures should be developed
to discover moisture conditions and mold growth at the
earliest stages and take action quickly. In the event
that amplification has occurred, remediation should
be performed by qualified personnel using established
guidelines to remove the mold, prevent recurrence, and
protect employees and the public.
For addition information on mold and microbial contamination,
please see the related XL Environmental Risk Bulletin
entitled, “Mold Prevention and Control for Mechanical
and HVAC Contractors.”
XL Environmental • Risk Control Division •
520 Eagleview Boulevard, PO Box 636, Exton, PA 19341
• Phone: 800-327-1414 • Fax: 610-458-7285
• xlenvironmental.com
XL Environmental is a division of XL Specialty Insurance
Company.
|